Detailed Selling Lead Description
Brand: telebahn
Model: 810_100
BT P C 255V
Main Features:
◎ Especially for 3+1 lines in TT system, installed between the port N and PE
◎ Standard single chip structure, high discharge capacity, pluggable
◎ Quick response
◎ Multifunctional terminals for connection of conductors and busbars
◎ Core components are from international well known supplier
Application:
For use in LZP 0B-1 or higher boundary. Prevent low voltage devices from surge . Applied in Class Ⅱ(Class C) power supply system, according to GB18802.1-2002/IEC 61643-1:1998-02.
Specifications:
Technical data
Rated voltage
(max. continuous voltage)
Uc
255V
Nominal discharge
current(8/20)
In
40kA
Max. discharge current
Imax
65kA
Voltage protection level
at In
Up
≤1.5kV
Follow current
extinguishing capability
at Uc
If
100Arms
Lightning impulse current
(10/350)
Iimp
12kA
Response time
tA
≤100ns
Operating
temperature range
-40℃…+80℃
Max. backup fuse
125A gl/gG
Cross-sectional area
1.5mm2~25mm2(solid)/35mm2(flexible)
Mounting on
35mm DIN rail
Enclosure material
purple thermoplastic, UL94-V0
Dimension
1 mod
Test standards
GB18802.1-2002; IEC61643-1:1998-02
Certification
CE